Gree · Mini-split · Cooling

Cooling and dry mode (multi-zone)

Multi21+

What happens, in order

  1. Compressor is stopped and one indoor unit reaches its cooling condition: the expansion valve, outdoor fan and compressor start
  2. The outdoor fan starts 5 s before the compressor and runs high for 3 minutes, then goes to its set speed; each speed is held at least 80 s
  3. When some indoor units are satisfied the compressor keeps running at the frequency required; satisfied units get their expansion valve closed
  4. When all indoor units are satisfied the compressor stops at once and the outdoor fan stops after 1 minute
  5. Switching to heating the 4-way valve is energized after the compressor has been stopped 2 minutes
  6. 4-way valve is off in cooling
  7. Dry mode follows the cooling start and stop rules; capacity demand per indoor unit is capped at 90 percent of its cooling value

Timings and thresholds

ItemValue
Outdoor fan lead5 s before compressor
Outdoor fan high-speed period3 min
Minimum time per fan speed80 s
Outdoor fan run-on1 min
4-way valve change delay2 min after compressor stop

Applies to: Gree Multi21+ multi-zone heat pump outdoor units

Models

MULTI18HP230V1COMULTI24HP230V1CO

More Gree mini-split sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Gree Multi21+ multi-zone service manual (MULTI18-24HP230V1CO), Function and Control sections 1 and 2. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.