Gree · Mini-split · Defrost
Forced (compulsory) defrost from the remote
What happens, in order
- Unit is running in heating at a set temperature of 16C
- Press + - + - + - on the remote within 5 seconds
- The unit enters forced defrost; the heating indicator on the indoor unit goes on 10 s and off 0.5 s repeatedly
- The outdoor unit defrosts using the normal defrost frequency and valve opening
- The unit leaves forced defrost on its own based on the actual defrost result and returns to normal heating
- If the unit has a fault or is stopped by a protection, forced defrost only works after that clears
Timings and thresholds
| Item | Value |
|---|---|
| Button entry window | 5 s |
| Start setpoint | 16C |
| Heating indicator pattern | ON 10 s / OFF 0.5 s |
Applies to: Gree Vireo GEN3 wall mini-split heat pumps 9k-24k; Kinghome KM09-12-18-24HT1DI and KM09-24HF1DI wall units
Models
More Gree mini-split sequences
- Compressor restart delay and minimum run time · Startup
- Anti-cold-air indoor fan delay · Heating
- Heating mode · Heating
- Heating mode (outdoor logic) and special modes · Heating
- Heating mode and anti-cold-air · Heating
- Heating, defrost, oil return and mode conflict · Heating
- Cooling and dry mode (multi-zone) · Cooling
- Cooling and dry mode with protections · Cooling
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Gree Vireo GEN3 service manual GREE_VIREOGEN3_SERVICE_090921 (3VIR 9-24k), Function and Control - outdoor unit modes; Kinghome KM09-12-18-24HT1DI service manual 6.2 (8); Kinghome KM09-24HF1DI service manual 6.2. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.