Gree · Mini-split · Cooling
Cooling, dry and fan modes (outdoor logic)
What happens, in order
- Cooling room at or above setpoint starts indoor fan, outdoor fan and compressor; 4-way valve stays off
- Room at or below setpoint minus 2C compressor stops and the outdoor fan stops 30 s later; between the two the unit keeps its previous state
- If the compressor stops on a fault in cooling, the indoor fan and swing carry on as before
- Dry room above setpoint starts compressor and outdoor fan with the indoor fan low; room at or below setpoint minus 2C stops the compressor, outdoor fan 30 s later; protections as in cooling
- Fan mode indoor fan runs at the selected speed (not Turbo); compressor, outdoor fan and 4-way valve stay off
Timings and thresholds
| Item | Value |
|---|---|
| Setpoint range | 16-30C |
| Stop point | Setpoint minus 2C |
| Outdoor fan run-on | 30 s |
Applies to: Gree Vireo GEN3 wall mini-split heat pumps 9k-24k
Models
More Gree mini-split sequences
- Compressor restart delay and minimum run time · Startup
- Anti-cold-air indoor fan delay · Heating
- Heating mode · Heating
- Heating mode (outdoor logic) and special modes · Heating
- Heating mode and anti-cold-air · Heating
- Heating, defrost, oil return and mode conflict · Heating
- Cooling and dry mode (multi-zone) · Cooling
- Cooling and dry mode with protections · Cooling
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Gree Vireo GEN3 service manual GREE_VIREOGEN3_SERVICE_090921 (3VIR 9-24k), Function and Control - outdoor unit modes. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.