Gree · Mini-split · Defrost
Automatic defrost
What happens, in order
- Defrost is considered after 45 minutes of continuous heating or 90 minutes of accumulated heating
- Entry also needs the outdoor coil to be cold enough for the outdoor air temperature: above 5C air with coil at -2C or lower; -2 to 5C air with coil at -6C or lower; -5 to -2C air with coil at -8C or lower; colder air uses a compensated comparison
- Defrost starts 3 minutes after the conditions are met
- Indoor fan and compressor stop
- 30 s later the outdoor fan stops
- 30 s later the reversing valve switches (de-energizes)
- 30 s later the compressor starts and ramps to defrost frequency (85 Hz)
- After 7.5 minutes of defrost, or if outdoor air is 10C (50F) or above, the compressor drops to 46 Hz
- 30 s later the compressor stops; 30 s after that the reversing valve switches back to heating
- 60 s later the compressor and outdoor fan restart and the indoor fan resumes under the anti-cold-air rules
- The remote shows H1 while defrosting (normal, not a fault); the indoor unit panel does not show it
Timings and thresholds
| Item | Value |
|---|---|
| Heating run before defrost | 45 min continuous or 90 min accumulated |
| Delay after conditions met | 3 min |
| Defrost frequency | 85 Hz |
| Maximum defrost time | 7.5 min |
| Exit frequency | 46 Hz |
| Restart delay after valve switch | 60 s |
Codes you may see during this
H1
Applies to: Gree Sapphire wall mini-split heat pumps
Models
More Gree mini-split sequences
- Compressor restart delay and minimum run time · Startup
- Anti-cold-air indoor fan delay · Heating
- Heating mode · Heating
- Heating mode (outdoor logic) and special modes · Heating
- Heating mode and anti-cold-air · Heating
- Heating, defrost, oil return and mode conflict · Heating
- Cooling and dry mode (multi-zone) · Cooling
- Cooling and dry mode with protections · Cooling
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Gree Sapphire 9-12k service manual (SAP09-12HP230V1A), Technical Information - Function and Control; Gree Sapphire 18-24k service manual (SAP18-24HP230V1A), same section. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.