Gree · Mini-split · Defrost

Automatic defrost

Livo GEN4

What happens, in order

  1. Defrost is considered after 45 minutes of continuous heating or 90 minutes of accumulated heating, when the outdoor coil is cold enough for the outdoor air temperature (for example air at 41F or above with coil at 28.4F or lower)
  2. Defrost starts 3 minutes after the conditions are met
  3. Indoor fan and compressor stop; 60 s later the outdoor fan stops
  4. 30 s later the reversing valve switches
  5. 30 s later the compressor starts and ramps to defrost frequency (70 Hz)
  6. After 10 minutes, or when the outdoor coil reaches 50F, the compressor drops to 46 Hz
  7. 30 s later the compressor stops; 30 s after that the reversing valve switches back
  8. 60 s later the compressor and outdoor fan restart; indoor fan resumes under anti-cold-air rules; H1 shows on the display

Timings and thresholds

ItemValue
Heating run before defrost45 min continuous or 90 min accumulated
Delay after conditions met3 min
Defrost frequency70 Hz
Maximum defrost time10 min
Exit frequency46 Hz

Codes you may see during this

H1

Applies to: Gree Livo GEN4 wall mini-split heat pumps 30k-36k

Models

4LIV30HP230V1A4LIV36HP230V1A

More Gree mini-split sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Gree Livo GEN4 30-36k service manual (4LIV30-36HP230V1A), Technical Information - Function and Control. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.