Bosch · Boiler · Freeze protection

Frost protection setup

Greenstar 3A

What happens, in order

  1. Heating system leave boiler on with the boiler high limit dial at 95 F (35 C) or higher
  2. Or leave boiler off, put approved anti-freeze in the heating water and drain the DHW circuit
  3. DHW tank leave boiler on, high limit at 95 F or higher and turn the DHW thermostat fully counterclockwise (50 F / 10 C)

Timings and thresholds

ItemValue
Minimum boiler high limit95 F (35 C)
DHW thermostat for tank frost protection50 F (10 C)

Applies to: Greenstar 3A series

Models

ZBR 21-3AZBR 42-3AZWB 28-3AZWB 42-3A

More Bosch boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Bosch Greenstar 6721853955 (2025-11) and 6721853953 (2025-11), Heatronic service functions and operation sections. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.