Bosch · Boiler · Domestic hot water

Combi comfort and economy modes

Greenstar 3A

What happens, in order

  1. Comfort mode (default) heat exchanger is kept warm so DHW is instant, boiler may fire with no draw
  2. Economy mode (ECO lit) burner fires only when DHW is drawn
  3. On demand quickly open and close a tap to signal the boiler, then wait a short time for hot water
  4. In comfort mode, after preheating or a DHW call ends, the plate heat exchanger is reheated only after the cycle time
  5. After a DHW draw, space heating stays blocked for the constant DHW period

Timings and thresholds

ItemValue
Cycle time keeping DHW hot (3.E)20-60 min, default 20 min
Constant DHW period (3.F)0-30 min, default 1 min

Applies to: ZWB combi models

Models

ZWB 28-3AZWB 42-3A

More Bosch boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Bosch Greenstar 6721853955 (2025-11) and 6721853953 (2025-11), Heatronic service functions and operation sections. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.