Water piping layout requirements

Mega-Q

What is going on

All water piping components are field supplied. The layout has to allow service of the cascade unit and protect the system from air, debris, and pressure swings.

Check in this order

  1. Install a piping connection and gate valve for cleaning on the circulating and hot water piping so the cascade unit can be serviced separately.
  2. Install an air vent valve wherever air can collect in the water piping.
  3. Install a strainer rated 60 mesh or finer on the inlet piping.
  4. Connect the hot water supply circulation circuit through a gate valve.
  5. Install a closed expansion tank and safety valve in the hot water supply circulation circuit.
  6. Insulate all water piping and apply anti-freeze measures to all water piping.
  7. Do not install equipment that removes residual chlorine. Chlorine-free water can allow bacteria to grow.

Applies to: Field water piping for Mega-Q systems

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Mega-Q installation manual, p. 20 and p. 21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.