Daikin · Water heater troubleshooting
Cascade unit power and transmission conduit entry
What is going on
Power and ground enter through a 1-3/8 in (34.5 mm) hole. Transmission to the tank control board and three-way valve circuit uses its own knockout.
Check in this order
- Remove the resin wall hole cover by squeezing its top and bottom and pulling it out.
- Open the knockout with a hammer or similar tool.
- Remove burrs and paint the opening with repair paint to prevent rust.
- Protect wiring passing the knockout with protective tape.
- Seal gaps with putty or similar material if small animals could enter the unit.
- Install the conduit with the mounting plate and a field-supplied lock nut.
Applies to: Mega-Q cascade unit
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin Mega-Q installation manual, p. 25. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.