Check phase balance and phase rotation

Mega-Q

What is going on

Voltage imbalance above 2 percent shortens unit life. Above 4 percent the unit shuts down and a malfunction code shows on the remote controller. Reverse phase stops normal operation.

Likely causes

  • Voltage imbalance above 2 percent
  • Voltage imbalance above 4 percent triggers shutdown
  • Reverse phase connection

Check in this order

  1. Measure the phase-to-phase voltage balance; it must be 2 percent or less.
  2. If the imbalance exceeds 4 percent, the unit will shut down; correct the supply before restarting.
  3. If the phase order is wrong, swap two of the three phases.
  4. If reverse-phase, lost phase, momentary blackout or on/off cycling is possible, fit a local reverse-phase protection circuit.

Applies to: Mega-Q three-phase power supply

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Mega-Q installation manual, p. 55. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.