Daikin · Water heater troubleshooting
Check phase balance and phase rotation
What is going on
Voltage imbalance above 2 percent shortens unit life. Above 4 percent the unit shuts down and a malfunction code shows on the remote controller. Reverse phase stops normal operation.
Likely causes
- Voltage imbalance above 2 percent
- Voltage imbalance above 4 percent triggers shutdown
- Reverse phase connection
Check in this order
- Measure the phase-to-phase voltage balance; it must be 2 percent or less.
- If the imbalance exceeds 4 percent, the unit will shut down; correct the supply before restarting.
- If the phase order is wrong, swap two of the three phases.
- If reverse-phase, lost phase, momentary blackout or on/off cycling is possible, fit a local reverse-phase protection circuit.
Applies to: Mega-Q three-phase power supply
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Mega-Q installation manual, p. 55. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.