Drainage and freeze protection on site
What is going on
Water drains from the bottom frame during operation and defrost. Cold outdoor temperatures can freeze the bottom frame and foundation.
Likely causes
- Condensation and defrost water drop through gaps in the bottom frame.
- Ground below freezing for long periods can freeze the bottom frame.
Check in this order
- If drain water is a problem, use a stand and a field supplied drain pan.
- In areas that stay below freezing for long periods, attach a drain pan heater (sold separately) to the heat source unit.
- Leave a gap between the bottom frame and the foundation surface so frozen ground does not reach the frame. In cold regions the manual recommends 20 in. (500 mm) to 40 in. (1000 mm).
- Provide a drainage ditch around the foundation so water does not collect around the system.
- In areas where the outdoor air can drop below freezing, drain the water from inside the cascade unit before switching off the breaker.
- Do not turn off the power immediately after stopping operation. Wait at least 5 minutes before switching off the power, or water leakage can occur.
Applies to: Heat source unit and cascade unit
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin Mega-Q installation manual, p. 9-10. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.