Transmission wiring layout and three-way valve circuit
What is going on
Up to six Mega-Q systems can share one water loop. Up to eight Mega-Q systems can be run from one tank controller kit. The tank control board's three-way valve circuit sends a defrost/freezing prevention signal. Its contact is a no-voltage contact rated 208/230 V, 10 mA to 2 A.
Check in this order
- Never connect power supply wiring to the transmission terminal.
- Wire the tank control board, heat source and cascade units per the transmission wiring diagram.
- For a closed hot water storage tank, connect the three-way valve circuit between X1 and X2 of the X1M terminal on the cascade unit board A7P.
- Limit each water loop to six Mega-Q systems and each tank controller kit to eight systems.
Applies to: Mega-Q multi-unit systems
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin Mega-Q installation manual, p. 27. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.