Temperature and pressure relief valve discharge line

Vitocell 100-V

What is going on

The T&P valve is supplied with the tank and must be installed to code. The discharge line must be safe for attendants and must not restrict flow.

Check in this order

  1. Install the T&P valve in the pipe connection point shown in the manual.
  2. Run the discharge line to a safe discharge point about 1 ft (305 mm) above the floor, close to a floor drain.
  3. Keep the discharge line as short as possible, pitch it downward from the valve, and end it plain, not threaded.
  4. Orient the discharge line so it does not scald people.
  5. Do not route the discharge line directly outdoors.
  6. Do not install any valve or restriction between the tank and the T&P valve, or between the valve and the discharge outlet.
  7. Have the owner operate the test lever at least once a year.
  8. Have the heating contractor re-inspect the T&P valve at least every three years.

Applies to: Vitocell 100-V CVWC T&P valve

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocell 100-V CVWC installation, service and operating instructions, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.