Temperature and pressure relief valve discharge line
What is going on
The T&P valve is supplied with the tank and must be installed to code. The discharge line must be safe for attendants and must not restrict flow.
Check in this order
- Install the T&P valve in the pipe connection point shown in the manual.
- Run the discharge line to a safe discharge point about 1 ft (305 mm) above the floor, close to a floor drain.
- Keep the discharge line as short as possible, pitch it downward from the valve, and end it plain, not threaded.
- Orient the discharge line so it does not scald people.
- Do not route the discharge line directly outdoors.
- Do not install any valve or restriction between the tank and the T&P valve, or between the valve and the discharge outlet.
- Have the owner operate the test lever at least once a year.
- Have the heating contractor re-inspect the T&P valve at least every three years.
Applies to: Vitocell 100-V CVWC T&P valve
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocell 100-V CVWC installation, service and operating instructions, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.