Viessmann · Water heater troubleshooting

Cleaning the inside of the DHW tank

Vitocell 100-V CVWC

What is going on

Cleaning the interior requires draining the tank and reassembling it with a new gasket. The water being drained may be hot.

Likely causes

  • Loose deposits or chemical build-up inside the tank

Check in this order

  1. Drain the domestic water from the DHW tank. The water may be hot.
  2. Remove the cosmetic cover, thermal insulation, inspection port flange cover and gasket.
  3. Disconnect the DHW tank from the domestic water piping to keep cleaning agents out of the pipework.
  4. Clean the interior with plastic tools only. Remove loose deposits with a pressure washer or by hand.
  5. Do not use pointed, sharp or hard objects, which can damage the interior surfaces.
  6. Remove stubborn build-up with a chemical cleaner if the pressure washer does not remove it.
  7. Drain all cleaning agent completely.
  8. Rinse the interior thoroughly after using chemical cleaners.
  9. Reconnect the DHW tank to the piping.
  10. Fit a new gasket under the inspection port flange cover.
  11. Install the inspection port flange cover and tighten to 18 lbft (25 Nm).
  12. Fill the DHW tank on the domestic water side.
  13. Insert the thermal insulation and reinstall the cosmetic cover.

Applies to: Vitocell 100-V CVWC

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocell 100-V CVWC installation, service and operating instructions, p. 29. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.