Daikin · Water heater troubleshooting
Snow protection for the outdoor unit
What is going on
In heavy snow areas, keep snow away from the coil and the air side so the unit can operate.
Likely causes
- Snow building up on the fins.
- Snow blocking the air inlet or outlet.
- Lateral snowfall reaching the heat exchanger coil.
Check in this order
- Install baffle plates on the air side of the outdoor unit to limit wind and snow exposure.
- Raise the bottom frame at least 19-11/16 in. (500 mm) above predicted snow level.
- Remove the coil guards in heavy snowfall so snow does not build up on the fins.
- Build a large canopy or pedestal if lateral snow can reach the coil.
- In low ambient temperature and high humidity, keep the drain holes clear, for example with the optional drain pan heater.
Applies to: Heat source unit in snow areas
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin Mega-Q installation manual, p. 10. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.