Daikin · Water heater troubleshooting

Set cascade unit address

Mega-Q

What is going on

Assign a unique address to each cascade unit using the push buttons on the cascade unit's 7-segment display.

Check in this order

  1. Power on the heat source unit, cascade unit and tank control board.
  2. Open the upper front panel of the cascade unit and the electrical component box service cover.
  3. In normal mode, hold the page break button (BS1) for more than 5 seconds to enter setting mode.
  4. Press the operation button (BS2) 13 times until the display shows the address table, then press the confirmation button (BS3).
  5. Use BS2 to select the address (1 to 8), then press BS3 to save. The display stops blinking and stays lit.
  6. Press BS3 again, then press BS1 to finish address setting.
  7. If confused, press BS1 to return to normal mode and start again from step 1.
  8. Close the service cover. Repeat for every cascade unit, numbering in ascending order with no duplicates.

Applies to: Cascade units

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Mega-Q installation manual, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.