Daikin · Water heater troubleshooting
Route wiring into the tank control board
What is going on
Power, ground and low-voltage wiring enter through the conduit holes at the bottom of the board. Keep the board and terminal block undamaged.
Check in this order
- Route power supply, transmission and sensor relay harness wiring to the tank control board.
- Fit a conduit into the 7/8 in. (22.2 mm) hole at the bottom of the board, for power, ground and low-voltage wiring.
- Protect the wiring with conduit where it passes through holes so the edges cannot damage it.
- Secure the power wiring with the attached clamp so no external force reaches the terminal.
- Seal the gap between the board and the conduit with putty or sealing material to keep small animals out.
Applies to: Mega-Q tank control board wiring
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Mega-Q installation manual, p. 57. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.