Daikin · Water heater troubleshooting

Release air from cascade unit water piping

Mega-Q

What is going on

Purge air from the water side of the cascade unit before test operation.

Likely causes

  • Air trapped in the circulating or hot water piping

Check in this order

  1. Open the lower front panel of the cascade unit.
  2. Open the gate valves on the circulating and hot water piping between the cascade and the storage tank so water can flow through the unit.
  3. Open both air release valves until only water comes out of the hose, then close the valves.
  4. Close the front panel when finished.

Applies to: Cascade unit water side

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Mega-Q installation manual, p. 41. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.