Mount sensors on existing tank flanges or pipes
What is going on
A thermistor body can be fitted to an existing flange or pipe on the tank. Sensor 3 sits near the hot water outlet, sensor 2 around the centre, and sensor 1 near the circulating water piping at the lower part of the tank.
Check in this order
- Remove the thermistor cover as described for wall mounting.
- Attach the thermistor body to the existing flange or pipe at the correct point.
- Place sensor 3 near the hot water outlet pipe at the top of the tank.
- Place sensor 2 around the centre of the tank.
- Place sensor 1 near the circulating water piping to the cascade unit, lower part of the tank.
- Insulate the tank and the sensor. Without insulation there is a burn risk and hot water supply temperature drops.
Applies to: Mega-Q hot water storage tank sensor locations
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Mega-Q installation manual, p. 54. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.