Navien · Water heater troubleshooting
Measuring inlet gas pressure
What is going on
Check the gas inlet pressure at full burn. For licensed professionals only.
Check in this order
- Shut off the manual gas valve on the supply line.
- Open a hot faucet so the unit fires and purges the gas line. Keep the faucet open until the unit shuts down from lack of gas, then close it.
- Remove the screw from the pressure test port on the unit gas inlet.
- Connect a manometer to the port and zero it.
- Reopen the manual gas valve and check all connections for leaks.
- Open several high-flow fixtures (tub, shower, kitchen sink) to bring the unit to maximum burn.
- At maximum burn, read the inlet pressure 3.0 to 10.5 in. WC for natural gas, 8.0 to 13.5 in. WC for propane.
- Confirm the maximum does not exceed the manufacturer value.
Applies to: CR and CC series water heaters
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien CR/CC installation manual, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.