Measuring inlet gas pressure

CRCC

What is going on

Check the gas inlet pressure at full burn. For licensed professionals only.

Check in this order

  1. Shut off the manual gas valve on the supply line.
  2. Open a hot faucet so the unit fires and purges the gas line. Keep the faucet open until the unit shuts down from lack of gas, then close it.
  3. Remove the screw from the pressure test port on the unit gas inlet.
  4. Connect a manometer to the port and zero it.
  5. Reopen the manual gas valve and check all connections for leaks.
  6. Open several high-flow fixtures (tub, shower, kitchen sink) to bring the unit to maximum burn.
  7. At maximum burn, read the inlet pressure 3.0 to 10.5 in. WC for natural gas, 8.0 to 13.5 in. WC for propane.
  8. Confirm the maximum does not exceed the manufacturer value.

Applies to: CR and CC series water heaters

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CR/CC installation manual, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.