Navien · Water heater troubleshooting
Add or remove a slave unit
What is going on
Use when changing the number of units in a cascade without changing the master.
Check in this order
- Power off all units.
- Add or remove the communication cable at the PCB.
- Power on the units, set DIP SW1 #1 and DIP SW2 #6-8 on the master to ON.
- Hold SW3 and SW4 on the master for more than 3 seconds, then perform the slave set-up.
- Return DIP SW1 and DIP SW2 to their original positions.
- Hold SW3 and SW4 on the master for more than 3 seconds to finish.
Applies to: Cascade systems
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: CR-CC installation manual, p. 37-38. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.