Navien · Water heater troubleshooting

Annual T&P relief valve maintenance

NWP500

What is going on

The T&P valve must be fitted and operated at least once a year so it does not stick. Water is extremely hot when discharged.

Check in this order

  1. Make sure no one is nearby before opening the valve.
  2. Open the T&P valve handle on the side of the water heater and drain 1–2 gallons.
  3. If no water comes out, turn the water heater off and contact a licensed professional or Navien Technical Support.
  4. Do not block the T&P valve discharge outlet.
  5. If the T&P valve leaks, install a PRV on the cold inlet (recommended 50–60 psi), add an expansion tank with the correct pressure, and adjust the temperature setting if needed.

Applies to: NWP500 series

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NWP500 installation manual, p. 64. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.