Keep R410A refrigerant piping clean, dry and tight

Mega-Q

What is going on

R410A is very sensitive to moisture, dust and oil. The system must be kept clean, dry and leak free.

Likely causes

  • Moisture or dust in the piping.
  • Mineral oil or flux contaminating the refrigerant oil.
  • Oxide scale forming inside pipes during brazing.

Check in this order

  1. Keep moisture and dust out of the piping. Pinch the pipe ends if the work lasts a month or longer, or pinch or tape them if it lasts less than a month.
  2. Take extra care when passing pipes through walls or holes to the outside.
  3. Do not use flux when brazing. Use phosphor copper filler B-Cu93P-710/795.
  4. Flush the pipe with nitrogen during brazing and use a pressure reducing valve set to about 3 psi (0.02 MPa).
  5. Do not use antioxidants when brazing.
  6. Charge R410A only in liquid form, because it is a blend.
  7. Do not use gauges, hoses, leak detectors or recovery equipment designed for conventional refrigerants.

Applies to: Field refrigerant piping on R410A side

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Mega-Q installation manual, p. 11-12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.