Internal wiring routing in the heat source unit

Mega-Q

What is going on

Keep wiring away from the compressor, high temperature piping and the gas stop valve, and keep ground wiring away from compressor leads to avoid electrical noise.

Likely causes

  • Electrical noise from ground wire touching compressor lead wiring
  • Wiring contacting compressor or hot piping

Check in this order

  1. Fix power and ground wiring to the back of the support with the attached clamp (2).
  2. Keep ground wiring off the compressor lead wiring.
  3. Keep wiring clear of the compressor and high temperature piping.
  4. Keep power wiring off the gas stop valve and front panel.
  5. Keep transmission wiring at least 2 in (50 mm) from power and ground wiring.
  6. After electrical work, confirm no connectors or terminals are disconnected in the electrical components box.

Applies to: Mega-Q heat source unit

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Mega-Q installation manual, p. 30-31. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.