Installing the pressure relief valve
What is going on
A pressure-only relief valve is required because the unit has a built-in temperature high limit switch. No valve is supplied with the unit.
Check in this order
- Install an approved 3/4 in., maximum 150 psi pressure relief valve on the hot water outlet, as close to the unit as possible.
- Confirm the valve discharge capacity is at least the maximum pressure rating of the water heater.
- Confirm the valve BTUH input rating is equal to or above the unit maximum input (for example, a CR-210 at 175,000 BTUH needs a valve rated at least 175,000 BTUH).
- Run the discharge tube to within 6 in. of the floor, with a free and full drain and no reducing coupling or restriction.
- Route the discharge so hot water cannot splash people or nearby equipment.
- Do not place any valve between the relief valve and the tank.
Applies to: CR and CC series water heaters
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien CR/CC installation manual, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.