Daikin · Water heater troubleshooting

Install water temperature sensors on the outer tank wall

Mega-Q

What is going on

Surface-mounted sensors are less accurate and the tape can come loose, so welding a short pipe to the tank is preferred. Accuracy depends on tank wall thickness, so the settings must be checked during trial run and after operation.

Likely causes

  • Tank wall thickness affects reading accuracy
  • Aluminum or SUS tape may come off

Check in this order

  1. Remove the thermistor cover so the thermistor body can be pulled out (loosen the screw first).
  2. Cut through the outer jacket and insulation over the sensor spot.
  3. Attach a short pipe to the surface of the inner tank, preferably by welding.
  4. Insert the thermistor body into the short pipe.
  5. Restore the outer jacket and insulation to their original state.
  6. Protect the thermistor from being dropped, from condensation and from water contact.

Applies to: Mega-Q tank wall-mounted water temperature sensors

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Mega-Q installation manual, p. 53. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.