Install the remote controller
What is going on
Mount and wire the NR-1ODU remote controller to the computer board.
Check in this order
- Turn off power to the water heater.
- Use at least 18 gauge wire, run no more than 300 feet.
- Connect 18 gauge wire to the remote controller terminals on the computer board; wire polarity does not matter.
- Do not connect 110-120 V AC to the remote controller.
- Feed the wire through the black rubber seal at the bottom right back corner of the case.
- Mount indoors only, out of children's reach, away from direct water, heat, humidity or steam.
- Do not disassemble the remote controller.
Applies to: Remote controller NR-1ODU
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: CR-CC installation manual, p. 33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.