Viessmann · Water heater troubleshooting

Install the DHW tank temperature sensor

Vitocell 100-V

What is going on

Sensor is mounted in the tank sensor well using the supplied mounting hardware.

Check in this order

  1. Carefully pull the sensor mounting hardware out of the tank sensor well.
  2. Mount the sensor on the outside of the sensor spring-clip, not in the center groove, so it is flush with the front of the clip.
  3. Push the sensor cabling into the groove of the mounting hardware.
  4. Push the sensor retainer with sensor into the sensor well as far as it will go.

Applies to: Vitocell 100-V CVWC DHW tank temperature sensor

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocell 100-V CVWC installation, service and operating instructions, p. 19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.