Viessmann · Water heater troubleshooting
Heating system connections for solar with extra tank
What is going on
Recommended piping for a solar application with an additional tank. The DHW temperature must be limited to 140°F (60°C) with an anti-scald tempering valve. The valve does not fully remove scald risk, so a mixing tap is recommended.
Check in this order
- For boiler supply temperatures over 203°F (95°C), remove the plastic supply and return grommets (left-threaded).
- Pipe the supply line with an incline and install an air vent valve at the highest point.
- For boiler supply temperatures over 230°F (110°C), install a type-tested high limit safety cut-out, unless one is already installed. Use a dual thermostat (high limit thermostat and high limit safety cut-out).
- Close off test nipples that are not used for a probe or sensor.
- Order the tee with sensor well for solar return separately.
Applies to: Vitocell 100-V CVWC with solar and boiler heating
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocell 100-V CVWC installation, service and operating instructions, p. 21. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.