Viessmann · Water heater troubleshooting

Heating system connections for solar with extra tank

Vitocell 100-V

What is going on

Recommended piping for a solar application with an additional tank. The DHW temperature must be limited to 140°F (60°C) with an anti-scald tempering valve. The valve does not fully remove scald risk, so a mixing tap is recommended.

Check in this order

  1. For boiler supply temperatures over 203°F (95°C), remove the plastic supply and return grommets (left-threaded).
  2. Pipe the supply line with an incline and install an air vent valve at the highest point.
  3. For boiler supply temperatures over 230°F (110°C), install a type-tested high limit safety cut-out, unless one is already installed. Use a dual thermostat (high limit thermostat and high limit safety cut-out).
  4. Close off test nipples that are not used for a probe or sensor.
  5. Order the tee with sensor well for solar return separately.

Applies to: Vitocell 100-V CVWC with solar and boiler heating

More water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocell 100-V CVWC installation, service and operating instructions, p. 21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.