Daikin · Water heater troubleshooting
Heat source unit knockout and conduit entry
What is going on
Power and transmission lines use separate knockouts on the front lower plate. Transmission runs on the left knockout. Hole sizes shown in the manual are 7/8 in (22.2 mm), 1-1/8 in (27.8 mm) and 1-3/8 in (34.5 mm).
Check in this order
- Choose a knockout whose size suits the conduit for the power and ground conductors.
- Use the left knockout (7/8 in / 22.2 mm) for transmission wiring in conduit.
- Remove burrs around the knockout holes.
- Protect the wiring with tape where it passes through.
Applies to: Mega-Q heat source unit
More water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin Mega-Q installation manual, p. 26. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.