Navien · Tankless water heater troubleshooting

No hot water when a fixture is opened

CR/CC

What is going on

Hot water is not available at the fixture.

Likely causes

  • No 120V 60Hz power supply
  • Gas supply valve not fully open
  • Water supply valve not fully open
  • Cold water inlet filter dirty
  • Hot water fixture not open enough to draw at least 0.5 GPM through the heater
  • Unit frozen
  • Not enough LPG in the tank (LPG installations)

Check in this order

  1. Confirm the unit has 120V 60Hz power.
  2. Confirm the gas supply valve is fully open.
  3. Confirm the water supply valve is fully open.
  4. Clean the filter on the cold water inlet.
  5. Open the hot water fixture far enough to draw at least 0.5 GPM through the water heater.
  6. Check whether the unit is frozen.
  7. Check that there is enough LPG in the tank.

Applies to: CR/CC series water heaters

More tankless water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CR/CC installation manual, p. 59. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.