Navien · Tankless water heater troubleshooting
Installation safety warnings
What is going on
Key install rules from the warnings section. Follow local codes and NFPA 54 or CSA B149.1.
Check in this order
- Install indoors only and never run the unit without vent piping connected.
- Make sure exhaust gases are fully expelled outside the building.
- Do not use the unit if any part was underwater. Have a qualified technician inspect it and replace any wet control or gas component.
- Do not reverse water and gas connections, as this can damage the gas valves.
- Provide drainage at the location. Navien is not responsible for leak damage without it.
- Use only for water heating and space heating.
- Use water treatment if the water is highly acidic or hard, to keep the warranty.
- Keep snow away from vent terminations and keep the vent and air intake clear.
- Do not overtighten fittings, which can crack pipe or fittings.
- Do not install where the unit is subject to vibration.
- Do not terminate the vent over walkways, near soffit or crawl space vents, or where condensate could cause damage.
- If overheating occurs or the gas supply does not shut off, close the manual gas valve to the unit.
Applies to: All CR and CC installations
More tankless water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien CR/CC installation manual, p. 11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.