Navien · Tankless water heater troubleshooting

Hot water temperature fluctuating

CR/CC

What is going on

Outlet temperature goes up and down.

Likely causes

  • Incoming cold water pressure too low (minimum 15 PSI)
  • Cold water inlet filter dirty
  • Gas line undersized
  • Supply gas pressure too low
  • Cross connection between cold and hot water lines

Check in this order

  1. Check that incoming cold water pressure is at least 15 PSI.
  2. Clean the filter on the cold water inlet.
  3. Confirm the gas line is sized correctly.
  4. Confirm supply gas pressure is adequate.
  5. Check for a cross connection between cold and hot water lines.

Applies to: CR/CC series water heaters

More tankless water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CR/CC installation manual, p. 59. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.