Navien · Tankless water heater troubleshooting
General venting rules
What is going on
Carbon monoxide hazard if vented wrong. Vent per the local code and the ANSI Z223.1/NFPA 54 or CAN/CGA B149.1 installation code. Plastic vent is allowed except when incoming or recirculation return water exceeds 160 F (70 C). Above 160 F setpoint with an external recirculation loop or combination heating, use Navien stainless or a 3-inch Category IV system (typically Type BH special gas vent, UL 1738/S636).
Check in this order
- Keep the vent run as short and straight as possible.
- Mount the heater as close to the vent terminator as practical.
- Never common-vent with another gas appliance or vent stack.
- Slope the vent up toward the terminal at 1/4 inch per foot (2% slope).
- Seal every joint airtight from flue collar to terminator, for exhaust and air intake.
- Keep the seam of horizontal vent runs on top.
- Do not downsize the vent pipe.
- Keep flammable materials away from the terminator.
- Terminator must be at least 12 inches above grade.
- Support the vent every 5 feet and with hangers per code; the vent weight must not rest on the heater.
- Do not connect any other appliance to the venting system.
Applies to: CR-180/210/240 and CC-180/210/240 series
More tankless water heater guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien CR-CC installation manual, p. 24-25. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.