General venting rules

CR/CC

What is going on

Carbon monoxide hazard if vented wrong. Vent per the local code and the ANSI Z223.1/NFPA 54 or CAN/CGA B149.1 installation code. Plastic vent is allowed except when incoming or recirculation return water exceeds 160 F (70 C). Above 160 F setpoint with an external recirculation loop or combination heating, use Navien stainless or a 3-inch Category IV system (typically Type BH special gas vent, UL 1738/S636).

Check in this order

  1. Keep the vent run as short and straight as possible.
  2. Mount the heater as close to the vent terminator as practical.
  3. Never common-vent with another gas appliance or vent stack.
  4. Slope the vent up toward the terminal at 1/4 inch per foot (2% slope).
  5. Seal every joint airtight from flue collar to terminator, for exhaust and air intake.
  6. Keep the seam of horizontal vent runs on top.
  7. Do not downsize the vent pipe.
  8. Keep flammable materials away from the terminator.
  9. Terminator must be at least 12 inches above grade.
  10. Support the vent every 5 feet and with hangers per code; the vent weight must not rest on the heater.
  11. Do not connect any other appliance to the venting system.

Applies to: CR-180/210/240 and CC-180/210/240 series

More tankless water heater guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien CR-CC installation manual, p. 24-25. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.