Carrier · Mini-split troubleshooting

Zero crossing detection error

D5FSFA

What is going on

If the zero crossing interval is wrong for a continuous 240 s, the unit stops and the LED shows the failure. The correct interval is between 6 and 13 ms.

Check in this order

  1. Check the power supply to the indoor unit for a valid AC zero crossing signal.
  2. Restart the unit and check that the fault does not return.

Applies to: D5FSFAH 9K to 16K

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FSFAH service manual, p. 14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.