485 communication fault (S1, S2)
What is going on
Communication between the indoor and outdoor main PCBs over the 485 signal wires fails.
Likely causes
- Interference from lamps or power transformers
- Signal wire too long or broken
- Shield cable not grounded
- Signal wires not seated on the PCB
- Faulty indoor or outdoor main PCB
Check in this order
- Power off, then restart the unit 2 minutes later.
- Check for interference such as many lamps or power transformers, and check whether the signal wire is too long.
- Check whether the signal wire is broken and replace it if so.
- Check that the signal wire is shielded and the shield is grounded. Use shielded cable if needed.
- Check that the signal wires are fully inserted into the PCB. Pull them out and reinsert them.
- Remove the interference or add a magnet ring on the power wire.
- Replace the indoor main PCB. If the error persists, replace the outdoor main PCB.
Applies to: Indoor and outdoor units
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FSCAH / D5FLCAH service manual, p. 37. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.