24K/36K/48K: water collector and water level switch removal
What is going on
Removes the water collector and water level switch from the indoor unit. Ventilation ring and collector are removed first, then the level switch is taken out of the collector subassembly.
Check in this order
- Remove the 2 screws holding the ventilation ring.
- Remove the 2 screws that fix the water collector.
- Remove the 5 screws of the water collector subassembly.
- Turn the water collector subassembly over and remove the water level switch.
Applies to: 24K/36K/48K size indoor units
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FSCAH / D5FLCAH service manual, p. 72-73. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.