Work area checks before opening a flammable refrigerant circuit

D5FSCAH / D5FLCAH

What is going on

R454B is flammable. Make the area safe before any work that opens the refrigerant circuit or involves hot work.

Check in this order

  1. Check the area with a refrigerant detector suited to flammable refrigerants, before and during work.
  2. Keep ignition sources away, including smoking, and post NO SMOKING signs.
  3. Make sure the area is open or well ventilated and keep ventilation working during the work.
  4. Keep a dry powder or CO2 fire extinguisher next to the charging area when hot work is done.
  5. Make sure the work area is clear of flammable hazards before starting.

Applies to: Any work on the refrigerant circuit

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FSCAH / D5FLCAH service manual, p. 7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.