Carrier · Mini-split troubleshooting

Water discharge (drain) test

D5FSOAH

What is going on

Checks that the condensate drain works before the ceiling is closed. Run it in the new room before the ceiling is finished.

Likely causes

  • Incorrect water discharge pipe layout causes excessive water flow and a water level error.

Check in this order

  1. Before the test, make sure the drain pipe is smooth and every joint is sealed.
  2. Connect power and set the unit to cool mode. Check the sound of the drain pump.
  3. Keep cool mode running for at least 10 minutes.
  4. Stop the unit, wait 3 minutes, then check for anything unusual.
  5. Keep adding water until the high water level alarm triggers. Check that the drain pump removes the water right away.
  6. If the water level does not drop below the warning level after 3 minutes, the unit shuts down. Turn off the power, drain the water with the drain plug, and refit the test cap.
  7. Make sure the drain plug is properly plugged during normal operation to prevent leaks.

Applies to: D5FSOAH indoor unit

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FSOAH installation manual, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.