Carrier · Mini-split troubleshooting
Voltage checks at start-up
What is going on
Check voltages at the outdoor disconnect, outdoor terminal block and indoor unit before running the system.
Check in this order
- Measure 1(L1) to GND and 2(L2) to GND at the outdoor unit disconnect.
- Measure the same points at the outdoor unit terminal block.
- Measure 1(L1) to 2(L2) at the outdoor terminal block.
- Measure 1(L1) to GND, 2(L2) to GND, 1(L1) to 2(L2), and 2(L2) to 3(S) at the indoor unit.
- Record readings on the Voltage Check section of the start-up checklist.
Applies to: Single zone ductless start-up
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FCFA installation manual, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.