Carrier · Mini-split troubleshooting
Two dashes (--) on the indoor display in multi-zone AUTO
What is going on
AUTO CHANGEOVER on multi-zone systems can put an indoor unit in STANDBY. Standby is shown as two dashes and turns that unit off until all units match mode.
Likely causes
- AUTO mode used on a multi-zone system.
- Indoor units are in different modes (COOLING vs HEATING). HEATING is the system priority mode; simultaneous heating and cooling is not allowed.
Check in this order
- Set all indoor units to the same mode (COOLING or HEATING).
- Use AUTO only on single-zone systems.
- Confirm the dashes clear once all units match.
Applies to: Multi-zone systems
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FSFAH Owner’s Manual, p. 3. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.