Daikin · Mini-split troubleshooting
Thermostat ON/OFF control logic
What is going on
Thermostat control uses the difference between room thermistor temperature and target temperature, split into zones A, B and C. Thermostat OFF happens in zone A. Thermostat ON happens when the difference returns to zone C, or after the monitoring time in zone B. Zone boundary values differ for cooling and heating.
Check in this order
- Thermostat OFF when the temperature difference enters zone A.
- Thermostat ON when the difference comes back to zone C after being in zone A.
- Thermostat ON after returning from defrost, or when leaving zone A.
- Thermostat ON when the difference stays in zone B for the monitoring time, 10 minutes in cooling or 10 seconds in heating.
Applies to: FTXM-W/V cooling and heating
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SiUS042113EA service manual, p. 46. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.