Temperature sensor open or short circuit check (EH60, EH61, EH62, EH65, EH66, EC52, EC53, EC54, EC56)

D5FSOA

What is going on

A sensor is faulty when the sampled voltage is below 0.06 V or above 4.94 V.

Likely causes

  • Open or shorted sensor
  • Loose or damaged sensor wiring
  • Faulty PCB input

Check in this order

  1. Disconnect the temperature sensor from the PCB.
  2. Measure the sensor resistance with a multimeter.
  3. Compare the reading with the sensor resistance table in the appendix (p. 64).
  4. Check the connection between the sensor and the PCB. Fix wiring if needed.
  5. If the reading is outside the acceptable range, replace the sensor.
  6. If the sensor and wiring are good, replace the indoor PCB (EH codes) or outdoor PCB (EC codes).

Applies to: D5FSOAH sensors

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FSOAH service manual, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.