Carrier · Mini-split troubleshooting
System evacuation and charging
What is going on
Evacuate tubing and indoor coil with a 500 micron deep vacuum, or use the triple evacuation method if the pump cannot reach 500 microns and the system holds no liquid water. Always break vacuum with dry nitrogen. Factory charge in the outdoor unit covers up to 25 ft (8 m) of line; longer lines need added refrigerant up to the allowable length.
Check in this order
- Tighten the flare nuts fully before connecting.
- Connect the manifold gauge charge hose to a charge port on the low side service valve.
- Connect the charge hose to the vacuum pump, fully open the low side of the manifold, and start the pump.
- Evacuate by deep vacuum (500 micron) or triple evacuation.
- For triple evacuation pull down to 28 inHg, run the pump 15 more minutes, close valves, and break vacuum with dry nitrogen to 2 psig.
- Let the system stand for 1 hour, then repeat the nitrogen and evacuation cycle as shown in the service figure.
- When evacuation is complete, close the manifold low side and stop the pump.
- For lines over 25 ft (8 m), add refrigerant up to the allowable length.
- Disconnect the charge hose, fully open service valves B and A, and tighten the valve caps.
- Never use the compressor as a vacuum pump.
Applies to: D5FCFAH
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FCFAH service manual, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.