Carrier · Mini-split troubleshooting
Start-up checklist: electrical, piping and charge checks
What is going on
Items the start-up checklist asks the technician to verify and record for a single-zone ductless system.
Check in this order
- Record unit model and serial numbers for the outdoor and indoor units and check that they are compatible.
- Record wire size and type, and confirm there are no breaks, splices or wire nuts between outdoor and indoor units.
- Check the voltage at the outdoor disconnect, outdoor terminal block, and indoor unit for L1-L2, L1-GND, L2-GND and the signal line (3(S)).
- Leak check the system, then hold 500 psig (max. 550 psi) with dry nitrogen for at least 30 minutes.
- Evacuate using the triple evacuation method or the deep vacuum method as in the manual, and confirm the system holds 500 microns for 1 hour.
- Confirm the line set diameter matches the evaporator connections, and for conventional fan coils confirm it matches the outdoor unit size.
- Measure the liquid line length, calculate the additional charge, and record the final charge amount.
- Run the system at least 10 minutes at the set point and record T1, T2, T3, T4, Tb, Tp, Th and LA/Lr with the wireless remote Point Check function.
- Record any indoor or outdoor error codes present at start-up.
Applies to: D5FSOAH single-zone ductless system
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FSOAH installation manual, p. 26-27. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.