What is going on

Safety requirements from the manual for work on R-454B circuits. Follow national and local codes.

Check in this order

  1. Confirm the technician holds a current certificate for handling refrigerants.
  2. Check the area with a refrigerant detector that is suitable for flammable refrigerants before and during work.
  3. Keep the work area well ventilated and keep ignition sources away, including smoking.
  4. Have a dry powder or CO2 fire extinguisher at the charging area if any hot work is done.
  5. Check that the refrigerant charge matches the room size and that ventilation openings are clear.
  6. Use only a leak test method with sensitivity of 1/8 oz (5 g)/year or better. Do not use a halide torch or open flame to find leaks.
  7. Recover all refrigerant before brazing, or isolate the leak section with shut-off valves.
  8. Purge the circuit with oxygen-free nitrogen. Never use compressed air or oxygen.
  9. Pressure test field piping with inert gas for at least 1 hour with no pressure drop.
  10. Evacuate so the pressure does not rise above 1500 microns within 10 minutes. The vacuum target is the lesser of 500 microns or the local code value.
  11. Charge by the liquid method only, use short hoses, and avoid overfilling.
  12. Ground the system before charging and label the system when charging is complete.
  13. Do not use means to speed up defrosting or cleaning other than those the manufacturer recommends.

Applies to: D5FSFAH ductless system with R-454B refrigerant

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FSFAH owner's manual, p. 3-5. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.