Service procedure for flammable refrigerant (R-454B)
What is going on
Required practice when working on a system that contains A2L flammable refrigerant R-454B.
Check in this order
- Only certified personnel may break into the refrigerant circuit.
- Ensure the work area is open or well ventilated before breaking into the system or doing hot work, and keep ventilation running during the work.
- Do not use a halide torch or any naked-flame detector to look for leaks.
- Recover all refrigerant into correct recovery cylinders before opening the circuit.
- Purge the circuit with oxygen-free nitrogen. Do not use compressed air or oxygen.
- Evacuate, then break the vacuum with nitrogen, and repeat until no refrigerant remains.
- Charge by the liquid method only, with short hoses.
- Ground the system before charging and label it when charging is done.
- Do not overfill. Pressure test with OFN before recharging.
- Leak test after charging and again before leaving the site.
- Keep vacuum pump outlet away from ignition sources.
- Do not use means other than the manufacturer-recommended ones to speed defrost or clean the unit.
Applies to: R-454B systems
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FSOAH installation manual, p. 3, 5-6. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.