Service procedure for flammable refrigerant (R-454B)

D5FSOAH

What is going on

Required practice when working on a system that contains A2L flammable refrigerant R-454B.

Check in this order

  1. Only certified personnel may break into the refrigerant circuit.
  2. Ensure the work area is open or well ventilated before breaking into the system or doing hot work, and keep ventilation running during the work.
  3. Do not use a halide torch or any naked-flame detector to look for leaks.
  4. Recover all refrigerant into correct recovery cylinders before opening the circuit.
  5. Purge the circuit with oxygen-free nitrogen. Do not use compressed air or oxygen.
  6. Evacuate, then break the vacuum with nitrogen, and repeat until no refrigerant remains.
  7. Charge by the liquid method only, with short hoses.
  8. Ground the system before charging and label it when charging is done.
  9. Do not overfill. Pressure test with OFN before recharging.
  10. Leak test after charging and again before leaving the site.
  11. Keep vacuum pump outlet away from ignition sources.
  12. Do not use means other than the manufacturer-recommended ones to speed defrost or clean the unit.

Applies to: R-454B systems

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FSOAH installation manual, p. 3, 5-6. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.