Carrier · Mini-split troubleshooting
Select piping exit direction and knock-out panel
What is going on
Four exit directions are available: left-hand side, left rear, right rear, and right-hand side. The drain hose is recommended on the right-hand side when facing the back of the unit. Side exits should come out horizontally so the lower panel can be installed.
Check in this order
- Choose the exit side based on the wall hole position relative to the mounting plate.
- If the wall hole is behind the unit, keep the knock-out panel in place.
- If the wall hole is at the side, remove the plastic knock-out panel on that side, using needle-nose pliers if needed.
- Cut the knock-out panel only as needed for the actual pipe size.
- Route the pipes so the unit sits against the wall after installation.
Applies to: Indoor unit D5FSHA 6K to 36K
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FSHA installation manual, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.