Carrier · Mini-split troubleshooting

Removing refrigerant and evacuating before opening the circuit

D5FSCAH / D5FLCAH

What is going on

Follow this order when breaking into the refrigerant circuit.

Check in this order

  1. Remove refrigerant safely following local and national rules.
  2. Evacuate the system.
  3. Purge the circuit with oxygen-free nitrogen. Purging is optional for A2L.
  4. Evacuate again. This step is optional for A2L.
  5. When using flame to open the circuit, keep flushing with inert gas.
  6. Do not use compressed air or oxygen to purge.
  7. Break vacuum with oxygen-free nitrogen, fill to working pressure, vent to atmosphere, then pull down again. Repeat until no refrigerant is left.
  8. Vent to atmospheric pressure before work on the system.

Applies to: Repairs that open the refrigerant circuit

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FSCAH / D5FLCAH service manual, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.