Carrier · Mini-split troubleshooting
Removing refrigerant and evacuating before opening the circuit
What is going on
Follow this order when breaking into the refrigerant circuit.
Check in this order
- Remove refrigerant safely following local and national rules.
- Evacuate the system.
- Purge the circuit with oxygen-free nitrogen. Purging is optional for A2L.
- Evacuate again. This step is optional for A2L.
- When using flame to open the circuit, keep flushing with inert gas.
- Do not use compressed air or oxygen to purge.
- Break vacuum with oxygen-free nitrogen, fill to working pressure, vent to atmosphere, then pull down again. Repeat until no refrigerant is left.
- Vent to atmospheric pressure before work on the system.
Applies to: Repairs that open the refrigerant circuit
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FSCAH / D5FLCAH service manual, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.