Refrigerant recovery, purge and evacuation before opening circuit
What is going on
Required sequence for flammable refrigerant work on the circuit.
Check in this order
- Recover refrigerant safely into correct recovery cylinders per local and national rules.
- Evacuate the system.
- Purge the circuit with oxygen-free nitrogen.
- Evacuate again.
- Flush or purge with nitrogen when using flame to open the circuit, then open the circuit.
- For purging, break vacuum with oxygen-free nitrogen, fill to working pressure, vent, then pull vacuum; repeat until no refrigerant remains.
- Vent to atmospheric pressure before work. Keep the vacuum pump outlet away from ignition sources.
Applies to: Flammable refrigerant service
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FSHA installation manual, p. 6. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.